Most electricians are referred to as “indoor wiremen” and are experts
at installing electrical equipment indoors, but some lack experience
working with exposed cables and outdoor equipment bonding. Traditional
methods of bonding and grounding include the extensive use of bare
copper conductors for equipment bonding.
While copper is preferred for
bonding steel, it is not the best choice around exposed aluminum
members. Aluminum and copper should not come into direct contact due to
galvanic corrosion issues. Over time, copper has a tendency to erode
aluminum and can even cause structural failure of thin aluminum
extrusions when in direct contact.
Even though the National Electric Code (NEC) supports the bonding
of PV module frames to their metal support structures, this method has
only recently become widely accepted by the PV industry and authorities
having jurisdiction (AHJs). While this practice was common for PV system
installations during the 1980s and 1990s, extra focus on bonding
aluminum PV module frames in the mid-2000s caused many jurisdictions to
question whether this practice was appropriate. During the mid-2000s,
methods that connected each PV module to an equipment grounding
conductor became the widely accepted method. This was primarily due to
installation information found in many PV modules’ manufacturing
literature for products listed to UL 1703, the safety standard for PV
modules.
Over the past few years, a new safety standard has been under
development, UL 2703, entitled, “Mounting Systems, Mounting Devices,
Clamping/Retention Devices, and Ground Lugs for Use with Flat-Plate
Photovoltaic Modules and Panels.” One of the main reasons for the
development of this standard was to have a method to evaluate bonding
methods that a mounting system may employ to address the requirements of
NEC 690.43.
Review of TUV Field Evaluation Report
In November 2014, TUV performed testing on bonding equipment in place
at the Mandalay Bay Convention Center 6.4-MW PV array in Las Vegas,
Nevada. The equipment at the test site was the Unirac RM Roof Mount
low-sloped roof mounting system. The field evaluation report provided by
TUV, dated December 1, 2014, was based on the procedure set forth in
the Bonding Path Resistance test in Section 13 of UL 2703.
Test site on the Mandalay Bay Convention Center rooftop in Las Vegas. Credit: Unirac.
This test requires a 4-wire design that uses two conductors to inject
current into the test sample and another two conductors to measure the
resultant voltage drop from the current injection point to the current
receiving point. The worst case scenario was chosen for the bonding path
test by injecting current at one corner of a 150 x 150-foot PV array
and receiving the current at the opposite corner of the same array
approximately 210 feet away. A simple diagram of the test setup,
provided in the TUV report, is shown in Figure 1.
Figure 1: Test Setup for 150-foot by 150-foot Array. Credit: Unirac.
This bonding test shown in Figure 1 was duplicated with another test
using a 6 AWG solid copper equipment grounding conductor. Since the
copper conductor would typically be run around the perimeter of the
array, rather than through the array, the length of copper used was 315
feet to be consistent with conventional installation methods. The test
setup the solid copper wire is shown in Figure 2.
Figure 2: Test Setup for 315-foot and 150-foot Solid 6 AWG Copper Wire. Credit: Unirac.
During the test, an 11-amp current and a 33-amp current were injected
into the grounding circuit for each set of conditions. These two
currents were chosen to coincide with the requirements of UL 2703 and to
go well beyond those requirements, by a factor of 3. These currents
simulate not just a single ground fault in one string, but simultaneous
ground faults in 3 strings, which is much more than the standard
requires. It is interesting to note that the change in current had no
impact on the ground path resistance of either the bonded array or the 6
AWG copper conductor.
The key result from these tests was that the bonding path resistance
for the bonded array was 0.0034 ? (3.4 milliohms) versus 0.1245 ? (125
milliohms) for the 6 AWG copper conductor. The typical published
resistance values for 6 AWG copper is approximately 400 m? per 1000 feet
so a 315-foot conductor should have resistance of approximately 126 m?,
exactly what was measured. Clearly, the bonded array performed superior
to the solid copper conductor, by a factor of 36. This means that a
bonded RM PV array has 2.7 percent of the resistance of a solid copper 6
AWG conductor and will therefore carry 36 times as much current in a
fault condition. Since fault currents are typically quite low in a PV
array, and sometimes go undetected depending on the accuracy of a
ground-fault detector, the RM bonding method is more likely to detect
faults, resulting in a safer installation.
In addition to the worst-case test using a 150x150-foot array,
testing was performed on a smaller 75 x 150-foot array as seen in Figure
3. This testing was done to determine if there was any appreciable
change in the results from the bonding path resistance test. In this
case, the solid 6 AWG copper conductor was only 150 feet long for this
test given the small array section. Given the shorter bonding path for
both the array section and the solid copper, the bonding path resistance
was 2.2 m? for the array section and 57 m? for the solid copper. These
results are expected given the shorter paths of both systems. The array
section path distance was reduced from roughly 210 feet with the 150 x
150-foot array down to about 167 feet. This shorter distance was roughly
80 percent of the 210-foot distance and the ground path resistance
reduced to 65 percent of the original path resistance.
Figure 3: Test Setup for 75-foot by 150-foot Array. Credit: Unirac.
The reason for large improvement in ground path resistance with the
bonded array is because the resistance of a single path is simply the
series resistance of the conductor — normally a copper conductor like
solid 6 AWG. A bonded metal structure has literally thousands of current
paths from one point to another point. Each of these different paths is
in parallel, rather than series, with one another. Parallel resistors
add according to the reciprocal of their resistance so the resistance
always goes down with parallel resistance paths. With thousands of
parallel paths, the resistance drops significantly.
Closeup of the bonded array at the test site in Las Vegas. Credit: Unirac.
Finally, with thousands of paths, comes the benefit of redundancy.
With a bonded metal array, dozens of connections can be broken and there
will be almost no change in ground path resistance. The many other
paths simply take slightly more current. With a single equipment
grounding conductor, a single connection can be broken and everything
that the wire was connected to can become ungrounded. When a conductor
is run 315 feet, rather than 3 feet from the bonded array to a ground
bus in a combiner box, the probability that a failure occurs in that 315
feet is much more likely than a failure in the shorter 3-foot section.
In Conculusion
In summary, bonding systems, tested to UL 2703, represent a large
improvement in the performance and ease of meeting the equipment
grounding requirements of the NEC. AHJs need to understand the benefits
of these types of bonding and grounding configurations since these tests
show that they are superior to conventional methods often used in the
field today. The benefits of a bonded PV array are not only in
ground-fault detection, but also in lower touch voltages, and better
redundancy. In addition to better compliance with the intent and
language of the NEC, bonding methods are much easier for the installer
to install properly.
One of the major field problems with PV systems today is that archaic
bonding and grounding methods are often difficult to perform properly
in the field. This means that mistakes and bad connections are extremely
common. PV array mounting methods that use products specifically
designed to create electrical bonds at each connection point will ensure
long-lasting safety for the exposed metal parts of a PV array.
Given the likelihood that exposed cables may become damaged over the
20-30 year life of a PV system, having well-bonded and grounded PV array
structures is key to the long-term safety of PV systems.
PV System Equipment Bonding and Grounding Requirements
Article 690 in 2014 version (and the 2011 version) of the National Electric Code (NEC) and states the following:
“(A) Equipment Grounding Required. Exposed
non–current-carrying metal parts of PV module frames, electrical
equipment, and conductor enclosures shall be grounded in accordance with
250.134 or 250.136(A), regardless of voltage.”
This section references two important sections in Article 250,
Grounding and Bonding, sections 250.134 and 250.136(A), restated below:
“250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed).
Unless grounded by connection to the grounded circuit conductor as
permitted by 250.32, 250.140, and 250.142, non–current carrying metal
parts of equipment, raceways, and other enclosures, if grounded, shall
be connected to an equipment grounding conductor by one of the methods
specified in 250.134(A) or (B).
(A) Equipment Grounding Conductor Types. By connecting to any of the equipment grounding conductors permitted by 250.118.
(B) With Circuit Conductors. By connecting to an
equipment grounding conductor contained within the same raceway, cable,
or otherwise run with the circuit conductors.
Exception No. 1: As provided in 250.130(C), the equipment
grounding conductor shall be permitted to be run separately from the
circuit conductors.
Exception No. 2: For dc circuits, the equipment grounding
conductor shall be permitted to be run separately from the circuit
conductors.
Informational Note No. 1: See 250.102 and 250.168 for equipment bonding jumper requirements.
Informational Note No. 2: See 400.7 for use of cords for fixed equipment.”
“250.136 Equipment Considered Grounded. Under the
conditions specified in 250.136(A) and (B), the normally
non–current-carrying metal parts of the equipment shall be considered
grounded.
(A) Equipment Secured to Grounded Metal Supports.
Electrical equipment secured to and in electrical contact with a metal
rack or structure provided for its support and connected to an equipment
grounding conductor by one of the means indicated in 250.134. The
structural metal frame of a building shall not be used as the required
equipment grounding conductor for ac equipment.”
http://www.renewableenergyworld.com/rea/news/article/2015/04/bonded-pv-arrays-could-provide-safer-solar-power?page=2
No comments:
Post a Comment